What are the adjustment ranges for SQUARE D Class 9013GHG2 pressure switch?
The pressure range of a class 9013 GHG2J30 is adjustable, however ALL settings must fall withing the allowable adjustment range parameters as detailed below.
- The CUT-OUT can be set within 60 to 200 PSI
- The CUT-IN can be set within 40 to 170
- The differential range is 20-40 PSI
Copied below is the chart for the 9013GHG2 adjustable ranges published on page 40 of the attached Schneider Electric /Square D Catalog.
https://download.schneider-electric.com/files?p_Doc_Ref=9034CT9701
For example, the following pressure range settings are within the adjustment parameters.
60 CUT-IN to 80 CUT-OUT (20 PSI differential)
60 CUT-IN to 100 CUT-OUT (40 PSI differential)
170 CUT-IN to 190 CUT-OUT (20 PSI differential)
160 CUT-IN to 200 CUT-OUT (40 PSI differential)
However, the settings below are NOT within the published parameters.
60 CUT-IN to 79 CUT-OUT (19 PSI differential is out of range)
60 CUT-IN to 101 CUT-OUT (41 PSI differential is out of range)
180 CUT-IN to 200 CUT-OUT (20 PSI differential – however the cut in is out of range)
40 CUT-IN to 81 CUT-OUT (41 PSI differential – however the cut out is out of range)